A real section through one floor-to-floor
Tight PT slab
Drag the slab underside, the beam bottom, the duct bottom or the floor line. Use the buttons for concrete or steel and for routing the duct under or through the beam. Arrow keys edit the same values.
Section through one floor · 400 ft of perimeter · 12 floors · $110 per SF of facade
Clear height: 108 in · Structure below slab: 0 in · Duct: 10 in · Slab: 7 in · Concrete · Duct below the beam
Assumptions, not a structural or code design. Floor-to-floor = finish floor 1.5 in + slab + plenum + ceiling assembly 2 in + clear height. Plenum = structure below the slab + services below it. A duct hung under the structure sits 2 in below it, with 1 in of insulation on each side and 3 in of clearance above the ceiling grid. A duct may pass through a beam web opening only if its insulated height is at most half the beam depth (an assumed limit); the plenum is then the beam depth plus 3 in. A 4 in sprinkler main rides in the bay and never sets the depth. Sections are drawn schematically. Facade cost assumes a 400 ft perimeter (120 × 80 ft), 12 floors and $110 per SF of facade, and ignores everything else that scales with height. Slab dead load assumes normal-weight concrete at 150 lb/ft³; a composite deck's 1.5 in flutes count as half concrete, plus about 3 psf of deck. The reference is the tight PT slab.